| MODEL |
9010 |
9020 |
9030 |
9050 |
9075 |
| Power Rating (P.F.=0.8) |
1000VA / 800W |
2000VA / 1600W |
3000VA / 2400W |
5000VA / 4000W |
7500VA / 6000W |
| AC Input |
Voltage |
230V
± 15% |
| Frequency |
50Hz
± 3Hz |
| Phase |
Single
Phase |
| Battery |
D.C.
Voltage |
48V
/ 72V / 180V / 192V |
| Type |
SMF
or TUBULAR |
| Back-up
Time |
As
per the requirement |
| Protections |
Battery
low cut-off. Battery Current limit. |
| Recharge
Time |
About
5 hours after fully discharged |
| AC output |
Voltage |
230
V ± 2% (adjustable) |
| Frequency |
50Hz
± 0.5% |
| Voltage
Regulation |
±2 |
| Frequency
Stability |
±0.5% |
| Power
Factor |
>0.7
lagging to unity |
| Harmonic
Distortion |
<3%
T.H.D. at linear load |
| Overload
Capacity |
110%
for 20 seconds |
| Inverter
Operation |
PWM
giving pure sine wave output |
| Efficiency |
|
>80% |
| Meters |
|
Moving
iron meter for output voltage
Moving iron meter for output current. |
| LED indications |
CHARGER
ON |
GREEN
LED |
| INVERTER
ON |
YELLOW
LED |
| BATTERY
LOW |
RED
LED |
| OVER
LOAD |
RED
LED |
AUDIO ALARM &
PROTECTIONS |
MAINS
FAIL |
AUDIO
ALARM |
| DC
UNDER VOLTAGE |
UPS
TRIP |
| DC
OVER VOLTAGE |
MAINS
TRIP |
| OVER
LOAD |
UPS
TRIP |
| OUTPUT
AC OVER VOLTAGE |
UPS
TRIP |
| OUTPUT
AC UNDER VOLTAGE |
UPS
TRIP |
| Environment |
Temperature |
0º
C - 40º C |
| Relative
Humidity |
0%
- 95% (non condensing) |
Physical Dimensions
(mm)
(W * D * H) |
380 * 560 * 680 |
450 * 700 * 850 |
450 * 700 * 850 |
550 * 775 * 990 |
850 * 775 * 900 |
| Weight ( Without
Battery) |
100 kg |
140 kg |
160 kg |
200 kg |
350 kg |